Quick Answer: The voltage drop formula comes from Ohm’s law. For single phase it is 2 times resistivity times length times current, divided by cable area. For three phase, use root three instead of 2. Divide by supply voltage for a percentage and compare it with the code limit.
Key takeaways:
- Voltage drop is just current times the resistance of the cable.
- Single phase uses a factor of 2, three phase uses about 1.732.
- You can rearrange the formula to find the smallest cable size.
- Copper and aluminium differ by roughly 1.6 times in resistivity.
- Verify limits against current Indian code and consult a licensed electrician.
Formulas scare many beginners, but the voltage drop formula is only Ohm’s law in a longer dress. If you know that voltage equals current times resistance, you already know the core idea. The rest is working out the resistance of a cable of a given length and size.
This article explains each part of the formula, shows how to rearrange it, and works through three examples set in India with 230V and 415V supplies, copper and aluminium cables, and prices in rupees.
The Starting Point: Ohm’s Law
Ohm’s law says that voltage equals current times resistance. When current flows through a cable, the cable acts as a small resistor. The volts lost across that resistor are the voltage drop. If you want to refresh the basics, an ohms law calculator lets you try the relation with your own numbers.
The resistance of a wire depends on three things. It rises with length, falls as the wire gets thicker, and depends on the metal. In words, resistance equals resistivity times length, divided by cross-section area. Put that into Ohm’s law and you have the voltage drop formula.
The Three Main Formulas
Which formula you pick depends on the supply. Single phase and DC use the out and back path. Balanced three phase uses root three, which is about 1.732.
| Supply | Drop in volts |
|---|---|
| 230V single phase | 2 times rho times L times I, divided by A |
| 415V three phase | 1.732 times rho times L times I, divided by A |
| DC (solar, battery) | 2 times rho times L times I, divided by A |
Here rho is resistivity in ohm sq mm per metre, L is one-way length in metres, I is current in amperes and A is the cable area in sq mm. For this guide we assume copper at 0.0175 and aluminium at 0.0282, both at 20 degrees C. Hot cables have higher resistance, so verify with the maker’s data.
Percentage drop
Percent drop equals drop in volts divided by supply voltage, times 100. Use 230 for single phase and 415 for three phase. Codes talk in percent, so this last step is what you compare against the limit.
Rearranging the Formula for Cable Size
Most of the time you do not know the cable size. You know the load, the length and the drop you can allow. Turn the formula around and it gives the minimum area directly. For single phase, area equals 2 times rho times L times I, divided by the allowed drop in volts.
For three phase, swap the 2 for 1.732. The answer is rarely a standard size, so round up to the next available one. Indian cables come in 1.5, 2.5, 4, 6, 10, 16, 25 and 35 sq mm, and you cannot buy 2.65 sq mm, so you step up to 4.
What About Temperature and Power Factor?
The simple formula ignores two things. Resistance rises as a cable warms, by about 0.4 percent for every degree C. A cable running near 70 degrees C has roughly 20 percent more resistance than the 20 degree value used above.
Motors and other inductive loads also add reactance, and power factor changes the real drop. For short runs in small cables the effect is minor. For big three phase feeders, engineers use cable tables in millivolts per ampere per metre, which already include these effects.
The table method
Cable makers publish a figure in mV per A per m. You multiply it by current and length, then divide by 1000 to get volts. It is quick and accurate because the maker has already built in temperature and reactance. Many BIS-marked cable catalogues in India print these tables, so ask your dealer for one.
Worked Example 1: Geyser Circuit
A 3 kW geyser in a Delhi bathroom sits 40 m of cable away from the board on a 230V supply. Current is 3000 divided by 230, about 13.04 A. The limit is 3 percent, which is 6.9 V.
Minimum area equals 2 times 0.0175 times 40 times 13.04, divided by 6.9. That gives 18.26 divided by 6.9, or 2.65 sq mm. The next standard size is 4 sq mm copper. At an assumed Rs 48 per metre, 40 m costs about Rs 1,920 for each core.
Worked Example 2: Copper Against Aluminium
A 20 kW three phase load at 415V with power factor 0.85 draws 20000 divided by (1.732 times 415 times 0.85), which is about 32.7 A. The cable is 60 m long, and the limit is 3 percent of 415, or 12.45 V.
For copper, area equals 1.732 times 0.0175 times 60 times 32.7, divided by 12.45. That is 59.5 divided by 12.45, or 4.78 sq mm, so choose 6 sq mm. For aluminium, use 0.0282. The top line becomes 95.8, and 95.8 divided by 12.45 gives 7.7 sq mm, so choose 10 sq mm.
Aluminium needed a size about 1.6 times larger, matching the ratio of the two resistivities. Aluminium cable is cheaper per metre, but the bigger size and larger lugs narrow the saving. Current carrying capacity must also be checked separately.
Key takeaway: Drop depends on resistance only through the ratio of resistivity to area. To keep the same drop, aluminium needs about 1.6 times the area of copper.
Using the Formula on Solar and Battery Cables
The same formula works on DC wiring, but the numbers are much smaller in volts and much larger in percent. A battery bank at 48 V has far less room for loss than a 230V house circuit, because 1 V is already about 2 percent of the supply.
Take a home backup system in Lucknow with a 48 V battery, a 40 A load, 5 m of one-way cable and 16 sq mm copper. Drop equals 2 times 0.0175 times 5 times 40, divided by 16. That is 7 divided by 16, or 0.44 V, which is 0.91 percent of 48 V. This passes a 1 to 2 percent target that solar installers commonly use. With 6 sq mm the drop would be 1.17 V, or 2.4 percent, which is too high for comfort.
The lesson is that short DC runs still need thick cable when current is high. Always run the sum for the battery side, the panel side and the AC side separately.
Worked Example 3: Checking a Measured Drop
You can also run the formula backwards on a real site. In a shop in Indore, a multimeter reads 230 V at the distribution board and 214 V at a socket at the far end while a heater is on. The drop is 230 minus 214, which is 16 V.
Percent drop equals 16 divided by 230, times 100, or 6.96 percent. That is well above a 3 to 5 percent limit. Now use the formula to find the cause: a 2000 W heater draws about 8.7 A, so the loop resistance is 16 divided by 8.7, about 1.84 ohm. That suggests a very long run, a thin cable or a loose joint. Check terminals first, because a loose connection is cheaper to fix than new cable.
Putting the Formula to Work
Typing every sum by hand gets tiring when you compare several sizes. A free voltage drop calculator runs the same formula in a second, so you can test 2.5, 4 and 6 sq mm in turn. Use it as a check on your hand work, not as a replacement for understanding it.
Benefits of Knowing the Formula
When you understand the formula you can spot a bad design at a glance. You see that doubling the length doubles the drop, and doubling the area halves it. That simple feel helps you question a quote before you pay for it.
- You can size cable yourself and check a contractor’s choice.
- You can compare copper and aluminium fairly.
- You can find the cause of dim lights and weak motors.
- You can save money by avoiding both thin and oversized cable.
Challenges and Limitations
The basic formula assumes a steady load and a balanced three phase system. Real homes have loads that switch on and off, and real farms often run unbalanced. Starting current for pumps and compressors can be six times the running current and briefly causes a deep dip.
Resistivity values also shift with temperature and with the exact alloy. Cable data sheets and the National Electrical Code of India (NEC 2011) give more careful numbers. Treat any hand result as a first estimate and verify it.
Common Mistakes
- Forgetting the factor of 2 in single phase and DC circuits.
- Using root three on a single phase circuit.
- Entering length in feet or total cable length rather than one-way metres.
- Using the wrong resistivity for aluminium and copper.
- Rounding the cable size down instead of up.
- Ignoring that the limit applies to the whole path, not only the last cable.
Best Practices
- Write down your assumptions: resistivity, temperature margin and limit used.
- Round the cable size up to the next standard sq mm.
- Use the maker’s mV per A per m table for large feeders.
- Check both the voltage drop and the current rating of the cable.
- Buy BIS-marked cable and check its printed size and brand.
- Have a licensed electrician approve the final design and do the work.
Conclusion
The voltage drop formula is Ohm’s law applied to a long cable. Single phase and DC use a factor of 2, three phase uses 1.732, and everything else is length, current, resistivity and area. Rearranged, it gives the smallest cable you can use. Practise with the three examples above, then confirm your result with a calculator. Electrical work carries real risk, so consult a licensed electrician and verify limits against the current code.
- Try the free Voltage Drop Calculator →
- How to Calculate Voltage Drop (Step by Step)
- What Is Voltage Drop? A Simple Guide
- Voltage Drop Calculator: Free Online Tool and Guide
- Voltage Drop Examples for Beginners
- Resistor Color Code Examples for Beginners
- Pipe Weight Calculator: Free Online Tool + Guide
- More Engineering & Electrical guides
FAQs
Why is there a 2 in the single phase voltage drop formula?
Current must travel to the load and come back, so it passes through twice the one-way length of cable. The 2 accounts for both conductors. Forgetting it halves your answer.
How do I find the smallest cable for a given load?
Rearrange the formula: area equals the factor times resistivity times length times current, divided by the allowed drop in volts. Round up to the next standard size, then check the cable’s current rating too.
What resistivity should I use for copper and aluminium?
A common textbook choice is about 0.0175 for copper and 0.0282 for aluminium in ohm sq mm per metre at 20 degrees C. Real cables run hotter, so add a margin or use the maker’s data.
Is 3 percent a strict legal limit?
It is commonly quoted guidance from IS 732 and NEC 2011, and the limit may differ by case and supply authority. Always verify against the current code and ask a licensed electrician.